Case Study #109 | EPO Activated
Product | Liebert NX 30kVA |
Application | IT Data Room |
Synopsis | The client had a power outage, and the load was protected and switched to the generator. However, after the power was restored, the UPS would not come back online from bypass. |
Preliminary Actions | The client had a power outage, and the load was protected and switched to the generator. However, after the power was restored, the UPS would not come back online from bypass |
Resolution | Somewhere along the process of returning the UPS back to normal online operation from bypass mode, the Emergency Power Off (EPO) switch was activated, which caused the output contactor to remain open until it was reset. After going through the alarms with the client and verifying voltage, the Nationwide Power engineer was able to determine that there were no issues with the UPS. After resetting the EPO, the output contactor closed and the client’s load was restored. The Nationwide Power engineer verified the unit’s readings and ensured that the unit was online and protecting the critical load. |
Root Cause | Inadvertent activation of the EPO switch. |
Nationwide Power provides 24/7/365 technical support to ensure that everything operates and transitions successfully before, during, and after any power outage.
Request a quote Call | 800-868-2780 E-Mail
We are your critical power infrastructure partner!
Latest News
The Winter Advantage: Why Replacing UPS Batteries During Winter Is a Smart Move
News Article As the winter season approaches, it's an ideal time to contemplate the maintenance of your Uninterruptible Power Supplies (UPS) and, more specifically, the replacement of UPS batteries. UPS systems are a crucial component of safeguarding your...
Nationwide Power Honored as a Top Workplace for the Second Consecutive Year
News Article Corks are popping, and the excitement is overflowing at Nationwide Power as we celebrate a remarkable achievement. For the second year in a row, our organization has been named a Top Workplace, solidifying our position as a leader in creating a culture of...
Case Study #156 | Importance of Following Age Based Recommendations
Case StudyIn this Nationwide Power™ (NP™) case study, we highlight the importance of following your service provider’s age-based components. The most common age-based components are batteries (every 3-5 years), fans (every 5 years), capacitors (every 5-7 years), and...
Newsletter Signup
0 Comments