Case Study #117 | NPower and Tape Drive Power Supply
Product | Liebert NX Series UPS |
Application | Military / Datacenter |
Synopsis | Client found the alarms / condition of unit as: UPS in bypass, Inverter operating, unit unable to transfer online. |
Preliminary Actions | The client had a power outage, and the load was protected and switched to the generator. However, after the power was restored, the UPS would not come back online from bypass |
Resolution | Replaced blown output fuse along with other output fuses, tested UPS, placed system back online. |
Root Cause | One of the tape drives in the data center had a faulty / shorted power supply which was detected on the output of the UPS, enough so that it cleared an Output fuse on the UPS.
The UPS protected itself by clearing the fuse prior to allowing further damage to the Inverter. Note that periodic inspections should also be considered for the end user’s data center servers / tape drive equipment to insure proper operation within specifications. |
Images Credit: Images courtesy of IBM®
Nationwide Power provides 24/7/365 technical support to ensure that everything operates and transitions successfully before, during, and after any power outage.
Request a quote Call | 800-868-2780 E-Mail
We are your critical power infrastructure partner!
Latest News
The Winter Advantage: Why Replacing UPS Batteries During Winter Is a Smart Move
News Article As the winter season approaches, it's an ideal time to contemplate the maintenance of your Uninterruptible Power Supplies (UPS) and, more specifically, the replacement of UPS batteries. UPS systems are a crucial component of safeguarding your...
Nationwide Power Honored as a Top Workplace for the Second Consecutive Year
News Article Corks are popping, and the excitement is overflowing at Nationwide Power as we celebrate a remarkable achievement. For the second year in a row, our organization has been named a Top Workplace, solidifying our position as a leader in creating a culture of...
Case Study #156 | Importance of Following Age Based Recommendations
Case StudyIn this Nationwide Power™ (NP™) case study, we highlight the importance of following your service provider’s age-based components. The most common age-based components are batteries (every 3-5 years), fans (every 5 years), capacitors (every 5-7 years), and...
Newsletter Signup
0 Comments