Case Study
Case Study #115 | AP600 Fire Panel EPO
Product | Liebert AP600 Series UPS |
Application | Healthcare |
Synopsis | Customer called in with a report of the UPS being down and tripped off-line. Maintenance Bypass operation had taken place prior to arrival. Possible damage to equipment. |
Preliminary Actions | Upon arrival, found UPS in Maintenance Bypass Mode. Restart attempts were unsuccessful. |
Resolution | Replacement components had to be ordered to address possibly damaged components. |
Root Cause | Customer had the local Fire Department on site performing testing. The Fire Panel is tied to the UPS via shunt trip, and upon testing, the UPS was deactivated. Considering the Maintenance Bypass Panel was in use upon arrival, suspect this was operated in order to try and restore power back to the load, and possible internal UPS damage has occurred. Recommend customer give consideration to UPS 101 Critical Power customer training in order to better understand system functionality and operation, and also become familiarized with site-specific system functionality as it relates to facility operations. |
Nationwide Power provides 24/7/365 technical support to ensure that everything operates and transitions successfully before, during, and after any power outage.
Request a quote Call | 800-868-2780 E-Mail
We are your critical power infrastructure partner!
Latest News
The Winter Advantage: Why Replacing UPS Batteries During Winter Is a Smart Move
News Article As the winter season approaches, it's an ideal time to contemplate the maintenance of your Uninterruptible Power Supplies (UPS) and, more specifically, the replacement of UPS batteries. UPS systems are a crucial component of safeguarding your...
Nationwide Power Honored as a Top Workplace for the Second Consecutive Year
News Article Corks are popping, and the excitement is overflowing at Nationwide Power as we celebrate a remarkable achievement. For the second year in a row, our organization has been named a Top Workplace, solidifying our position as a leader in creating a culture of...
Case Study #156 | Importance of Following Age Based Recommendations
Case StudyIn this Nationwide Power™ (NP™) case study, we highlight the importance of following your service provider’s age-based components. The most common age-based components are batteries (every 3-5 years), fans (every 5 years), capacitors (every 5-7 years), and...
Newsletter Signup
0 Comments