Case Study
Case Study #113 | Failed Inductor
Product | Powerware 9315 80kVA |
Application | IT – Datacenter |
Synopsis | During regular preventive maintenance, found the input currents to be imbalanced as opposed to being balanced on previous preventive maintenance visit. |
Preliminary Actions | In performing further checks, and looking at the input currents at the input filter capacitors, found 0 amps of current on Phase ‘C’. Performed further checks and while looking through the top of the unit, discovered insulating wrap on the Phase ‘C’ of input inductor significantly burned. |
Resolution | Took the unit to Bypass Mode and isolated the [optional] Input Filter circuit by disconnecting contactor K6 in order to remove current flow through the inductor. |
Root Cause | Failed / faulty input capacitors going out of tolerance and causing excess heat at the inductor connection, or, failed / faulty input inductor. |
Nationwide Power provides 24/7/365 technical support to ensure that everything operates and transitions successfully before, during, and after any power outage.
Request a quote Call | 800-868-2780 E-Mail
We are your critical power infrastructure partner!
Latest News
The Winter Advantage: Why Replacing UPS Batteries During Winter Is a Smart Move
News Article As the winter season approaches, it's an ideal time to contemplate the maintenance of your Uninterruptible Power Supplies (UPS) and, more specifically, the replacement of UPS batteries. UPS systems are a crucial component of safeguarding your...
Nationwide Power Honored as a Top Workplace for the Second Consecutive Year
News Article Corks are popping, and the excitement is overflowing at Nationwide Power as we celebrate a remarkable achievement. For the second year in a row, our organization has been named a Top Workplace, solidifying our position as a leader in creating a culture of...
Case Study #156 | Importance of Following Age Based Recommendations
Case StudyIn this Nationwide Power™ (NP™) case study, we highlight the importance of following your service provider’s age-based components. The most common age-based components are batteries (every 3-5 years), fans (every 5 years), capacitors (every 5-7 years), and...
Newsletter Signup
0 Comments